Low price ESML2000 radio frequency admittance level switch for coal piles, crude oil tanks, raw material silos

The ESML2000 RF admittance level switch is a high-performance point-level material detection instrument designed based on the principle of RF admittance. By detecting changes in impedance and capacitance caused by materials between the probe and the silo wall, it enables accurate monitoring and alarm control of high and low levels for solids, powders, and liquids. The device features a built-in intelligent anti-clog shielding circuit that automatically eliminates interference from material adhesion, condensation, and dust on the probe surface, providing strong anti-interference capability and stable, reliable measurements. The product has no mechanical moving parts, motors, or blades, making it resistant to jamming and damage, with a long service life and minimal maintenance, suitable for continuous long-term operation. The entire unit uses a stainless steel probe with PTFE insulation for protection, making it dustproof, waterproof, corrosion-resistant, and wear-resistant. It supports high-temperature, high-pressure, and explosion-proof configurations, and is suitable for industries such as chemical, power, construction materials, food, pharmaceutical, and environmental protection. It can detect powders, granular materials, viscous materials, fly ash, medicinal liquids, wastewater, and other media. It is widely used for high-level overflow prevention and low-level material shortage interlock control in silos, storage tanks, ash bins, and reactors. The switch is easy to install, responds quickly, offers high cost-performance, and is an upgraded preferred choice to replace traditional rotary vane switches.[eos]

    Working Principle

    The admittance in radio frequency (RF) admittance is the reciprocal of impedance in electrical terms, comprising resistive, capacitive, and inductive components. RF refers to the high-frequency radio wave spectrum. When the instrument is operating, the sensor forms an admittance value with the tank wall and the medium being measured. As the material level changes, the admittance value changes accordingly. The circuit unit converts the measured admittance into a level signal output, enabling level measurement.

    Product Features

    1.High versatility: Capable of measuring liquid levels and material levels, meeting measurement requirements for different temperatures, pressures, and media. Measurement temperatures can reach up to 800℃, and pressures up to 5MPa, suitable for harsh environments such as corrosion and impact. 


    2.Anti-material adherence: The unique circuit design and sensor structure ensure that measurements are not affected by material clinging to the sensor, eliminating the need for regular cleaning and avoiding measurement errors. 


    3.Maintenance-free: There are no moving parts in the measurement process, eliminating mechanical wear issues and the need for maintenance. 


    4.Interference-resistant: Contact measurement provides strong anti-interference capability, overcoming the effects of steam and foam on measurements. 


    5.Accurate and reliable: Diverse measurement options make measurements more precise, unaffected by environmental changes, highly stable, and long-lasting.

     application scenarios

    1. Powder Industry (Strengths)
    Ultrafine powder, easily sticky powder: lime powder, coal powder, talc powder, flour, starch, medicinal powder
    Wet powder, moisture-absorbing powder, powder prone to adhering to silo walls

    2. Chemical Industry, Plastics
    PVC powder, PE powder, masterbatch, granules, resin, fertilizers, crystalline materials
    Corrosive raw material silos (not suitable for stainless steel or PTFE probes)

    3. Power, Environmental Protection
    Ash silos, dust removal ash, dry sludge, fly ash, biomass powder

    4. Food, Pharmaceuticals
    Powders, excipients, sugar, milk powder (hygienic grade probes)

    5. Can also measure
    Liquids, oil, wastewater, layered interfaces, foamy liquids (rotary paddle cannot measure at all)

    Product detail

    ESML2000- (3)ESML2000- (2)ESML2000- (1)

    Technical Specifications

    Product name

    ESML2000 RF admittance level switch

    Power supply voltage

    220VAC, 50/60HZ 24VDC

    Contact capacity

    SPDT 5A/240VAC

    Power consumption

    ≤2.5W

    Sensitivity

    ≤0.3PF

    Ambient temperature

    -40~80℃

    Medium temperature

    -40~800℃

    Temperature influence

    0.3PF/30℃

    Calibration

    Press the button to zero

    Alarm form

    Upper or lower limit

    Sensitivity settings

    1-9 gears

    Switch delay

    setting range 0-59S

    Shell protection

    IP65

    Leave Your Message