How to troubleshoot product problems?
How to troubleshoot and locate faults in PT100 temperature transmitter?
-
1. First, look at 3 types of typical fault phenomena
-
2. Check power supply and loop (basic 80% of faults)(1) Measure the terminals of the two-wire temperature transmitter: Check whether voltage is within the normal range of the transmitter: large line drop, insufficient power capacity, long-distance loss
(2) Measure output current: Fixed at 3.6mA: instrument self-test error, probe short circuit / fault Fixed at 4mA: PT100 open circuit, not connected, no temperature sensing Over 20mA: probe short circuit, motherboard damage Changes linearly with temperature normally: transmitter is fine, on-site process normal fluctuation -
3. Key determination to distinguish "probe fault" or "transmitter module fault"Fastest on-site isolation method:
Remove the three wires of the PT100 sensor and short-circuit the transmitter input If output returns to normal temperature zero point and is stable: PT100 probe itself is faulty Still error / erratic jump: temperature transmitter module itself is faulty Measure PT100 resistance (room temperature 25℃ standard) Normal:
≈109.6Ω Infinite:
platinum resistor open circuit Close to 0Ω:
short circuit Large deviation:
aging, moisture, water ingress -
4. Check wiring system (most common human error)Industrial requirement: three-wire PT100 Common errors:
(1) Use two-wire: wiring resistance adds up, temperature reading high, drift
(2) Three-wire misconnected, colors not distinguished, mixed: error of tens of degrees
(3) Three wires of different thickness, too long distance: compensation fails Key point: two wires of the same color in three leads are the compensation ends, must be connected to the transmitter compensation terminals simultaneously to eliminate cable resistance. -
5. Locate moisture, water ingress, condensation faults (high occurrence on site)Phenomenon:
value drifts, sometimes high sometimes low, worse in rainy weather Causes:
(1) Water ingress or condensation in junction box
(2) Poor sealing of protective tube, water vapor enters platinum resistor core Treatment:
dry, seal waterproof, replace waterproof connector, use glue for moisture protection -
6. Electromagnetic interference, grounding, shielding troubleshooting (main cause of erratic jumps)(1) Power cable and signal line in same conduit, close to inverter / motor → interference and erratic jumps
(2) Shielding layer grounded at both ends → ground loop, value fluctuation Correct method:
(1) Shielding layer grounded at one end (control cabinet side)
(2) Temperature control signal line in separate conduit away from power line
(3) In strong interference conditions, use isolated type temperature transmitter -
7. On-site zero / range drift calibration(1) Compare with standard thermometer at room temperature and observe deviation
(2) Local button or handheld operator:
(3) Correct zero drift
(4) Recalibrate range
(5) Deviation fixed and cannot be corrected: sensor aging, replace directly -
8. Safety precautions(1) Shut down and cool high-temperature equipment before disassembly to prevent burns
(2) Prohibit opening covers with power on or modifying wiring in explosion-proof areas
(3) In corrosive conditions, avoid medium exposure that could corrode skin
How to quickly locate and troubleshoot a malfunction in an ultrasonic flowmeter?
-
1. First classify three typical faults(1) No flow rate, no flow, zero display, weak signal → Probe coupling/pipe/medium/installation straight pipe section
(2) The flow rate jumps, fluctuates between large and small, and the values are fluctuating→ bubbles, scaling, interference, and incorrect installation
(3) Measurement is too large/small, inaccurate→ Parameter setting, range matching, sound velocity, and pipe wall input error -
2. Look at the instrument [signal strength / signal-to-noise ratio] core judgment (fastest)(1) Normal:
signal strength ≥ 80%, good signal-to-noise ratio, and stable value
(2) Low signal and no wave found: The coupling paste dries out, the probe is displaced, and the pipe rusts and scales too thickly The rubber lining/anti-corrosion layer is too thick, and the plastic pipe wall thickness parameters are selected incorrectly
(3) Signal intermittency: the medium contains bubbles, suspended solids, and pulsating water Treatment:
Reapply couplant, align the probe, polish the pipe wall, and correct the pipe parameters -
3. Investigation of media working conditions (80% on-site roots)(1) Liquid with bubbles/vaporization Phenomenon:
Readings jump, flow fluctuations, and instability Causes:
negative pressure at the pump inlet, pressure relief, pipeline intake, high temperature vaporization Solution:
Change the measurement point to the positive pressure area, away from the pump outlet/highest point of gas accumulation Exhaust and eliminate negative pressure suction
(2) Serious scaling, silt, and rust of pipes The external clip-on type is most feared: the sound absorption of the dirt layer→ poor penetration, and the measurement is small/immovable Solution:
clean the pipe wall, replace the measuring point, and switch to the pipe section type/electromagnetism
(3) Liquid accumulation in unfull pipes and pipelines It must be measured with a full tube, and if the tube is not full, it is directly inaccurate and there is no signal -
4. Installation & rigid verification of straight pipe section (high-frequency pit stepping)(1) Insufficient upstream straight pipe section (elbow, valve, reducer, pump) Requirements:
Standard: 10DN in the front, 5DN in the back The flow field → disordered→ runout and large error of the close resistance part
(2) The probe spacing and installation point are paired incorrectly The model (V method / Z method / W method) is selected incorrectly and the distance input is incorrect Re-use the instrument's built-in spacing calculation function to locate the punch hole
(3) Wrong installation orientation Horizontal tube: Probe mount at 3–4 o'clock on the side It is forbidden to install directly above (gas accumulation) and directly below (sediment) -
5. Parameter setting verification (large human error)Focus on 5 items:
(1) Pipe outer diameter, wall thickness, material (carbon steel / stainless steel / PPR)
(2) Lining thickness and whether there is anti-corrosion lining
(3) Sound velocity parameters of liquid type (water/sewage/oil).
(4) Range, unit, damping filter settings (the filter is too small and easy to skip, too large and slow to respond)
(5) Zero point calibration and static zero point drift compensation If one parameter is wrong, the error is directly more than ten percent. -
6. Electrical, interference and power supply investigation(1) Unstable power supply, large voltage drop→ Abnormal motherboard operation
(2) The signal line is not well shielded, and the power line of the frequency converter is in the same slot→ interfering and jumping Treatment:
Separate wiring and shielding single-ended grounding Stay away from motors, frequency converters, solenoid valves Install a signal isolator
Malfunctions and Solutions of Ultrasonic Level Gauge?
-
1. Core Diagnostic Entry Point: Check Echo Quality FirstMenu: Check Echo Strength / Signal-to-Noise Ratio Strong and Stable Echo: Instrument is basically normal; usually parameters / interference issues Weak, Missing, or Fluctuating Echo: Operational conditions, installation, or probe problems
-
2. Instrument Displays Normally, But Reading Remains 0 / Cannot Measure Liquid LevelCauses:
(1) Actual liquid level is within the blind zone (cannot be detected in the near field)
(2) Probe condensation, water droplet attachment, dust accumulation causing ultrasonic attenuation
(3) Large amount of foam, vapor, or mist on the liquid surface absorbing the sound wave
(4) Range set too small, working conditions exceed the range
(5) Tilted installation, probe facing tank wall / beam / pipe, causing false echo blockage Solutions:
(1) Check the blind zone, install higher or use a model with a smaller blind zone
(2) Clean the probe, add a purge / rainproof & dustproof cover / anti-condensation cover
(3) For foam / dense vapor conditions: switch to 80G radar / guided wave radar
(4) Recalculate range, leave 1.2 times margin
(5) Reinstall: position away from tank wall, obstacles, or feed inlets -
3. Erratic Values, Up-and-Down Drift, Fluctuating ReadingsCauses:
(1) Large liquid surface fluctuations, stirring, water impact disturbances
(2) Electromagnetic interference: frequency converters or motors in the same cable tray, poor grounding
(3) Filter damping set too low, response too fast
(4) Steel structures, ladders, or pipes inside the tank creating false echoes Solutions:
(1) Install stilling tube / flow guide tube to stabilize liquid surface
(2) Route signal line separately in conduit, single-end shield grounding, keep away from power/frequency lines
(3) Increase time damping / filter averaging in menu
(4) Enable false echo suppression, shield fixed interfering objects -
4. Inaccurate Readings for Static Empty / Full Tank, Zero Shift(1) Long-term temperature and humidity changes causing zero drift
(2) Water intrusion in probe or condensation in junction box causing moisture
(3) Ultrasound velocity temperature compensation failure Solutions:
(1) Execute zero calibration / empty calibration for static empty tank
(2) Dry and seal, replace waterproof joints with anti-moisture sealant
(3) Enable automatic temperature compensation to correct medium sound velocity -
5. Unstable Measurement in Tanks with Steam, Mist, or Volatile SubstancesCauses:
Water vapor or organic solvent mist absorbs ultrasound, scattering and attenuating the sound wave Solution:
Ordinary ultrasound is unsuitable for heavy steam; use frequency-modulated radar / guided wave radar -
6. Probe Corrosion, Aging, or No EmissionSymptoms:
No echo, silent probe, sensor fault error Solutions:
Check cable breakage, water ingress, breakdown; replace with corrosion-resistant PVDF probe -
7. Wiring and Power Supply IssuesSymptoms:
No display, current fixed at 3.6mA / 4mA / 22mA 3.6mA: Self-test fault, probe abnormal 4mA stuck: No echo, open loop 22mA: Overrange Solutions:
Measure actual DC24V power supply, check polarity, terminal oxidation, and shield grounding
How to quickly locate and troubleshoot gear flow meter malfunctions?
-
1. let's take a look at the rapid classification of three types of typical phenomena(1) No volume, no pulse, no movement, no accumulation→ jamming, blockage, no rotation, and empty pipeline
(2) The flow rate is small, the measurement is small, the error is large→ wear, viscosity is not matched, slippage, and bypass leakage
(3) Reading drift, going and stopping, loud noise, jitter, → bubbles, impurities jamming, pressure pulsation -
2. Quick judgment of the mechanical body (the fastest core)(1) Check whether there is medium flow on site, whether the front and rear valves are fully open, and whether the filter is blocked
(2) Touch the shell: Abnormal noise and vibration: gear jam impurities, bearing wear, dry wear No rotation, no shaking: jamming, no pressure at the inlet, and solidification of the medium
(3) Check the pre-Y-filter The filter is blocked→ there is a lack of liquid, the gear does not rotate, and the metering is stagnant Clean the filter and discharge pollutants regularly -
3. The meter does not count, the pulse has no output, and the instantaneous is 0 Common causes:(1) The medium contains large particles, iron filings, → gears are stuck
(2) Low temperature and high viscosity solidification, thickening in winter→ The gear belt cannot move
(3) The inlet pressure is too low, the negative pressure is suction, and the material is cut off
(4) The transmitting probe falls off, the Hall sensor is damaged, and the line is broken
(5) The internal bearing is worn and the rotor is bitten to death Resolution:
(1) Disassemble and clean the cavity and clean up impurities
(2) High viscosity medium is equipped with heat tracing and heat preservation
(3) Increase the inlet pressure difference and avoid negative pressure
(4) Check the pulse wiring, sensor clearance, and replace the transmitting component -
4. Inaccurate measurement, slowness, and lack of total amountCommon causes:
(1) Long-term use of gears/cavities wear, large gaps→ internal leakage and backflow
(2) If the viscosity of the medium is too low (such as water, dilute solvent), → slip slip volumetric failure
(3) Import and export loading reverse (easy to ignore)
(4) Insufficient pressure difference, insufficient load, and low-speed leakage
(5) Seal aging, bypass leakage Resolution:
(1) Switch to turbine/electromagnetic for low-viscosity media; High viscosity selection special clearance model
(2) Check the direction of the import and export arrows
(3) Serious wear and tear return to the factory for pairing grinding or replacement
(4) Check whether the pipeline bypass is leaking -
5. The meter head moves and stops, jumps, and intermittently measuresCommon causes:
(1) The medium is mixed with a large amount of air, bubbles, → idling false pulses
(2) Pipeline pulsation and pump intermittent oil supply
(3) The distance of the transmitting sensor is too far and the signal is intermittent
(4) Local slight jamming, sometimes jamming and sometimes rotating Resolution:
(1) Install exhaust valves upstream to eliminate air blockages
(2) Stabilize the pump pressure and add a buffer tank
(3) Adjust the Hall probe induction distance and shield the wiring to prevent interference -
6. Temperature and pressure related, inaccurate in winter, high temperature leakage(1) Low temperature: viscosity soars→ large resistance, difficult start, and no volume Install insulation jackets and heat tracing
(2) High temperature: seal aging and deformation, expansion gap increase→ internal leakage is large Replace high-temperature FKM / special seals -
7. Electrical signal fault location (remote transmission 4-20mA / pulse)(1) No pulse: broken probe, broken shielding wire, grounding interference at both ends of the shield
(2) Fixed current 4mA: no rotation signal, body not working
(3) Numerical jumping: strong frequency conversion interference and poor grounding Treatment:
(1) The signal line is routed separately and away from the motor frequency converter
(2) Single-ended grounding of the shielding layer
(3) Check whether the power supply DC24V is stable -
8. Daily prevention (90% reduction in failures)(1) The front end must be equipped with a precision filter
(2) It is strictly forbidden to use ultra-low viscosity pure water/dilute solvents for a long time
(3) High viscosity medium in winter insulation, shutdown and emptying
(4) Avoid idling, dry grinding, and liquid-free operation
Malfunctions and Solutions of Magnetic Resistance Floating Ball Liquid Level Sensor
-
1. Magnetoresistive float level sensor (rod type / analog 4-20mA) for accurate fault troubleshooting + solution on sitePrinciple: The float has a built-in magnet → the magnetoresistive sensing array in the probe rod senses the magnetic field → outputs the corresponding liquid level signal The five root causes of common problems are: float jamming, magnet demagnetization/detachment, water condensation in the probe, electromagnetic interference, and scale coating
-
2. 3 minutes of basic checks(1) Power supply wiring 24V DC as standard, the measurement voltage cannot be less than 18V; The terminals are not loose or oxidized; The shielded cable is grounded at one end, away from frequency converters and power cables, and it is forbidden to walk with the high-voltage bridge.
(2) Mechanical degrees of freedom The sensor is installed vertically (inclination angle <3°), and the float ball has no scaling, no debris jamming, no sticking, no winding, and smooth slide up and down throughout the process.
(3) Magnetic verification If you use an iron tool close to the float, the magnetic attraction is strong = the magnet is normal; Weak suction / no magnetic suction = magnet demagnetization, detachment, direct replacement of float.
(4) Sealing and waterproofing Junction box and cable inlet are free of condensation and water seepage; The probe rod is well sealed, and water ingress will directly burn the internal reluctance chip. -
3. High-frequency typical faults + symptomatic solutionFault 1: The liquid level is fixed and stuck at 0%/full scale Cause
(1) The float is stuck by silt, scale, and pipe wall, and cannot slide
(2) The magnet falls off, demagnetizes at high temperature, and the magnetic field coupling fails
(3) The magnetoresistive sensing element inside the probe rod is burned out and broken
(4) The range parameters are incorrectly modified, and the full zero point is misplaced
Solved
(1) Stop the machine to clean the tank, wipe the probe, dredge the float activity area, and install the guide anti-jam tube
(2) Detect the suction of the magnetic steel and replace the anti-corrosion float directly if it fails
(3) Manually toggle the float up and down, and the signal does not change → The probe assembly is scrapped and replaced
(4) Restore the factory settings and recalibrate the 4mA empty liquid level and 20mA full liquid level
Fault 2: Numerical runout drift, high and low instability Cause
(1) The liquid level tumbles, the water inlet impacts, and the float does not have a steady flow structure shaking
(2) On-site frequency conversion equipment and motors generate electromagnetic interference
(3) The probe rod is slightly damp, the insulation drops, and the signal is cluttered
(4) The instrument filter damping setting is too small
Solved
(1) Install a still water well/stabilizer to isolate the disturbance of water flow
(2) Optimize shielding grounding, install signal isolators, and increase the damping time of instrument software
(3) The drying junction box is waterproof and sealed, and the probe rod is directly replaced when water enters, and cannot be repaired
Fault 3: No output, black screen, 4mA unchanged all the time Cause power supply disconnection, reverse wiring, signal wire disconnection; the lowest level of the float card; The internal reluctance motherboard is damaged
Solved measured power supply voltage, fastening wiring calibration positive and negative poles; Manually raise the float out of the water body, synchronized current rise = normal, no change = sensor replacement
Fault 4: The high display is displayed all year round, and the full-scale alarm does not drop Cause The float is stuck in the upper limit, and the magnet is close to the probe; Internal circuit short circuit; Water ingress in the cavity
Solved Check for float card position faults; disassemble the junction box after power off to observe the condensation water traces; If there is water/short circuit, it will be replaced directly to rematch the installation stroke
Fault 5: Inaccurate measurement and error increase year by year Cause Probe rod/float fouling coating and shielding of magnetic field; installation tilt; Long-term high-temperature magnet attenuation
Solved Soft cotton cloth clean the surface scale with water (hard objects are not allowed to scratch the probe); Correction of vertical installation; The high-temperature medium is selected with high temperature resistance and strong magnetism, and the zero point range is calibrated once a year -
4. On-site minimalist self-test (no need to dismantle pipes)(1) No-load suspension: the float is ≈ 4mA to the end, the float is ≈ 20mA to the top, and the linear stable change = intact
(2) Magnetic test: iron adsorption float is strong = magnet is normal
(3) Shaking sound: There is a sound of water inside the probe = water inlet is scrapped
How to quickly locate and troubleshoot a malfunction in an electromagnetic flowmeter (3)
-
1. Pre-check: First confirm if measurement is possible
-
2. Three typical phenomenon classifications(1) Flow always 0, not moving, no display → power supply / wiring / empty pipe / excitation / electrode contamination
(2) Flow fluctuates, drifts, suddenly large or small → poor grounding / bubbles / interference / liner material adhesion
(3) Measurement too high or too low, cumulative inaccurate → pipe diameter and flow velocity mismatch, wrong parameters, zero point drift -
3. Basic electrical troubleshooting(1) Check power supply Two-wire DC24V actual measurement: 18–28V normal, low voltage causes crash or drift
(2) Check 4-20mA loop Fixed 4mA: no flow, empty pipe, electrode open circuit, excitation abnormal Above 20mA: range set too small, signal overload
(3) Wiring inspection Do not reverse positive and negative, terminals free from looseness and oxidation; Signal cables must not run in the same conduit with power / frequency conversion cables -
4. Empty/full pipe, electrode and liner faults (common)(1) Display empty pipe alarm, but there is water Electrode scaling, oil stain, attached insulating substances → signal acquisition failure Solution:
stop and flush, soak electrodes in weak acid to clean; scraping with hard objects is prohibited
(2) Pipe not full, negative pressure suction Creates false level, unstable electric field → erratic reading Correction: install lower, ensure full pipe year-round, vent high points
(3) Liner wear, peeling, bulging Long-term use with corrosive medium, insulation damage → internal short-circuit drift -
5. Step three: Grounding and excitation circuit (main cause of erratic readings)(1) No grounding ring on metal anticorrosive pipe / plastic pipe Cannot form reference potential → values fluctuate wildly Must be installed: stainless steel grounding ring / grounding electrode
(2) Shielding layer wiring wrong Should only ground one end at control cabinet, grounding both ends causes ground loop interference
(3) Excitation coil water ingress, insulation deterioration Performance: temperature rise, zero point drift, intermittent errors; needs drying or factory return -
6. Medium condition issues(1) Liquid contains many bubbles, sand Bubbles interrupt sensing signal → sometimes zero, sometimes large Solution:
vent upstream, install flow stabilizing tank
(2) High viscosity, wall-adhering crystals Electrodes covered, weak induction → measurement too low Solution:
regular flushing, use PTFE liner, self-cleaning structure -
6. Medium condition issues
-
7. Parameter calibration errors(1) Wrong pipe diameter, range, pulse coefficient → overall deviation
(2) Zero point not static calibrated → baseline exists under no load Solution:
stop, fill pipe, let static zero be cleared, empty pipe calibration -
8. Safety precautions(1) Do not disassemble sensor under pressure to prevent medium ejection
(2) Corrosive, high-temperature conditions should be stopped, cooled, and depressurized before maintenance
(3) Do not open covers with power on in explosive environments
Malfunctions and Solutions of Capacitive Liquid Level Gauge
-
I. Typical Faults(1) Liquid level does not move or is stuck at 4mA / fixed at a certain value
(2) Value drift, jumps erratically with changes in temperature or humidity
(3) Large deviation at no load, small deviation at full load, overall measurement error
(4) Direct over-range >20mA -
II. Rapid Electrical Circuit Diagnosis (Priority Troubleshooting)(1) Measure power supply: DC24V terminal actual voltage 18–28V Below 16V: large voltage drop, insufficient power load, causing drift or freeze
(2) Measure output current to determine status Constant 4mA: no change in probe, insulation breakdown, circuit disconnection, abnormal no-load recognition Constant >20mA: probe short-circuit, sheath damaged and damp, over-range Follows liquid level slowly but inaccurate: calibration / dielectric / material deposition problem
(3) Wiring & Shielding Signal lines should be independently threaded through conduits, away from inverter power cables; Shield layer should be grounded at one end (control cabinet), grounding at both ends causes circulating current and jumps; Check for oxidation, water ingress, or looseness at wiring terminals. -
III. On-site Quick Distinction Between "Instrument Head Fault" or "Probe Fault"Simplest isolation method:
(1) Disconnect on-site probe, perform simulated calibration / short-circuit check
(2) If instrument output changes normally → problem is with the probe itself on site
(3) If fault remains unchanged → replace conversion circuit board / instrument head -
IV. High-Frequency Core Issues — Probe Insulation, Moisture, Condensation, Anti-CorrosionDamage
(1) PTFE / PFA sheath cracking, scratching, aging Medium penetration, moisture → parasitic capacitance surge Symptom: zero point drift, reading at no load, the higher the temperature, the more it drifts Solution:
Check appearance, dry, reseal; probe must be replaced if damaged
(2) Junction box / sealing head condensation and water ingress Most common during rainy season or with steam tanks Symptom: value drifts slowly and irregularly Solution:
Drying, waterproof sealant, extended anti-moisture sealing gland, split installation (high-temperature steam) -
V. Material Deposition, Adhesion, Crystallization Causing False Liquid LevelOperating conditions: viscous liquid, slurry, sewage, scaling, humid powder Symptom: Tank shows high level even when emptied, liquid level does not drop, delayed readings Cause: film or probe deposits create fixed parasitic capacitance Solution:
(1) Clean probe surface of deposits
(2) Perform empty tank zeroing, deposit compensation, drift self-calibration
(3) For easily adhered materials: must use fully covered PFA, anti-adhesion, intelligent compensation type; ordinary capacitive probes cannot completely resolve -
VI. Dielectric Constant Mismatch Causing Measurement Inaccuracy(1) High dielectric (aqueous solution / acid-base): normal for standard models
(2) Low dielectric (oil products, organic solvents, dry plastic granules) Insufficient sensitivity, poor linearity, jumps Solution:
Enable low-dielectric gain parameters, special calibration; severe cases require replacing with RF admittance continuous level transmitter -
VII. Installation Interference Causing Abnormalities(1) Probe too close to metal tank wall, supports, stiffeners (<150mm) Electric field interference → jumps, deviation Correction: eccentric installation, away from metal structures
(2) Directly facing feed impact, stirring zone Material splashing, dynamic capacitance disturbance → reading jumps Correction: install protective sleeve, avoid feed drop area, increase software damping and filtering -
VIII. Zero / Range Calibration FailureLong-term usage, medium replacement, maintenance without re-calibration Manifestation: overall high/low readings, poor linearity Standard Operation: Calibrate zero with empty tank at rest → calibrate full-scale with full tank → confirm linearity follows
Float switch malfunction and solution
-
1. First, distinguish between the two commonly used structures(1) Cable-type float (commonly used in pump water tanks): internal steel ball contacts with swing angle
(2) Linkage reed switch float (multi-point control in industrial tanks): magnetic steel, reed switch induction -
2. Appearance and installation base inspection(1) Check if the housing is cracked, has water ingress, or leakage (internal short circuit due to water ingress / contact corrosion always causes failure)
(2) Check for cable jacket damage, pulling, soaking aging, terminal looseness and oxidation
(3) Check for installation jamming: against walls, blocked by pipes, entangled debris, the float cannot rotate freely
(4) Check if the medium temperature exceeds the rated value (PP generally ≤60°C, excessive temperature causes deformation and leakage) -
3. Float does not move, pump does not start / does not stop (contacts do not switch)Causes:
(1) Float is stuck by debris or pipe wall, cannot swing into position
(2) Internal steel ball / contacts oxidized, burned, or sticky
(3) Linkage type: magnetic steel fallen off, reed switch burnt, stuck in position
(4) Counterweight ball in wrong position, high and low level difference incorrectly set Troubleshooting:
(1) Manually swing the float, listen for internal rolling of steel balls
(2) No sound: internal stuck / damaged, replace directly
(3) Sound present but no power conduction: contact oxidized or burned
(4) Adjust counterweight ball position, remove external mechanical obstruction -
4. False action, frequent start/stop, erratic behaviorCauses:
(1) Water flow fluctuation, surge causing float to swing frequently and switch
(2) Internal contacts slight arcing, poor connection
(3) Cable too long, shaking or suspended swinging
(4) Linkage type: nearby steel structure magnetic field interference, float moving up and down Solutions:
(1) Add anti-surge tube, flow stabilizing baffle
(2) Control circuit add intermediate relay isolation (do not directly drive a high-power pump)
(3) Secure the cable, reduce suspended swing distance -
5. Housing water ingress, leakage failurePhenomenon:
intermittent, poor insulation, electric leakage, tripping Diagnosis: shake float and listen for water sound, surface condensation and whitening Solution:
Small sealed models cannot be repaired, replace directly; Do not pry open for repair, sealing failure will quickly recur -
6. Wiring and electrical matching issues(1) Normally open / normally closed reversed: water supply becomes drainage, logic reversed
(2) Directly driving high-power pump: contact current overload causes burn and sticking Correct method: float only controls the contactor coil, does not directly drive the main pump
(3) Voltage mismatch: AC220/DC24 mixed use, internal breakdown -
7. Corrosive environment aging failureAcid, alkali, sewage, chlorinated water: PP housing cracks, sealing ages, cable hydrolysis stiffens Solution:
replace with PVDF corrosion-resistant models, PUR corrosion-resistant cables
Malfunctions and Solutions of Radar Level Gauge
-
1. General pre-check(1) Power supply and wiring DC24V normal voltage drop≥18V; The terminals are not loose or oxidized; it is strictly forbidden to connect positive and negative; The shielded cable is grounded at one end, and it is not the same as the frequency converter and power cable.
(5) Grounding and anti-interference The instrument housing is independently protected and it is forbidden to connect to the neutral wire; The tank farm is isolated from frequency conversion mixing and pumps to avoid high-frequency clutter interference with 80G radio frequency.
(3) Core installation taboo (80G top priority) Stay away from the feed splash area, tank wall stiffeners, ladders, and baffles; The flange is coaxial in the center and not eccentric; Do not install in the center of the manhole; Avoid condensation, dripping, and dust from sticking to the horn antenna. -
2. Precise and radical treatment of high-frequency typical faultsFault 1: Empty tank shows liquid level, zero point is high, fixed false level Core Reasons: The 80G beam is extremely narrow, and it is easy to detect fixed echoes generated by flange end faces, tank bottom bosses, and antenna condensate/ash accumulation Resolution:
(1) Stop the machine to clean the horn antenna, dry the condensation, and blow off the dust;
(2) Execute the instrument menu: empty tank baseline calibration / false echo suppression (surface suppression), shield fixed interference echo;
(3) Modify the starting ranging and blind spot offset parameters, and ignore the interference of nearby flanges.
Fault 2: Large liquid level runout and frequent drift fluctuations Core Reasons: The liquid level tumbling, foam, volatile mist, tank vibration, and damping filter settings are too small Resolution:
(1) Menu increases software damping / echo average filtering time (3~10s);
(2) A large amount of foam/water vapor: 80G itself is adaptable, and if it is still unstable, you can add a waveguide/balance casing to stabilize the liquid level;
(3) Reinforce the mounting bracket to eliminate mechanical vibration; Rectify the shielding and grounding to isolate electromagnetic interference.
Fault 3: There is actual material, the instrument shows 0, and the liquid level cannot be detected Core Reasons: Low dielectric dielectrics (light oil, plastic particles), liquid level entering the near-field blind zone, antenna damage, range configuration reversal Resolution:
(1) Check the dielectric constant of the medium, and confirm that the low dielectric is selected as a high-gain 80G radar;
(2) Check the blind spot parameters and low cut-off distance of the instrument to avoid the liquid level falling in the measurement dead zone;
(3) Check the horn antenna for corrosion, cracking, deformation, and replace it directly if damaged;
(4) Correction range: empty can = zero point, full can corresponding to correct setting.
Fault 4: Antenna mounting, crystallization, and condensation lead to inaccurate measurement (80G Most Common Field Problems) Resolution:
(1) Sticky materials, easy to crystallize: purge type/anti-condensation horn, PTFE dust cover;
(2) Compressed air regularly purge the antenna, and it is forbidden to scratch the horn surface with hard objects;
(3) Large temperature difference in the tank produces condensation: increase the top of the tank insulation and anti-condensation steam accessories.
Fault 5: 4-20mA output is inaccurate, no current, and full-scale jamming Resolution:
(1) The measured circuit of the multimeter is on and off, and the short circuit, false connection, and line loss are checked;
(2) Reconfiguration: confirm that 4mA = empty liquid level, 20mA = full liquid level, and redo the current calibration;
(3) The line is normal but still has no output: the motherboard analog module is faulty, and the factory is returned for maintenance.
Fault 6: HART/Modbus communication cannot be connected Solution:
Unified device address, baud rate; check the positive and negative poles of the communication line; long-line matching terminal resistors; Stay away from sources of power interference.
How to troubleshoot and locate thermocouple faults
-
1. Basic 3-Minute Pre-Check(1) Inspect appearance and wiring Check for damaged insulation, water immersion, overheating, charred wires, terminal oxidation and blackening, loose crimping; Thermocouple compensating wires must not mix different types (K with K, E with E) and must not be connected randomly with regular copper wires.
(2) Check the cold junction (junction box / cabinet) Large cold junction temperature fluctuations, direct sunlight, heat, or proximity to cables can cause temperature drift and inaccurate readings.
(3) Check insulation and grounding Protective tubes damaged or damp, ceramic tubes cracked, thermometer elements leaking to ground. -
2. Four Typical Malfunction Symptoms, Causes, and Solutions(1) Instrument displays [Overrange, HH, OL, Maximum value] Common causes:
Thermocouple open circuit or burnt; compensating wire broken; terminal loose or internal ceramic tube breakdown. Handling: Power off and disconnect wires, use a multimeter in resistance mode to measure both ends of the thermocouple: Infinite resistance = burnt, replace thermocouple/temperature sensing element; High resistance = loose connection, retighten the crimp.
(2) Instrument displays [Negative, low, large temperature drift] Common causes:
Compensating wire polarity reversed (most frequent on site); Cold junction uncompensated, large cold junction temperature difference; Thermocouple aging, high-temperature annealing accuracy decline. Handling: Verify polarity, switch positive and negative; Enable instrument cold junction temperature compensation; Long-term high-temperature drift: replace with a new thermocouple.
(3) Temperature jumps, erratic readings, fluctuating high and low Common causes:
Poor terminal contact, vibration causing loose connection, damp leaking, interference (power lines of AC drives routed together) Handling: Tighten terminals, secure clips; Dry junction box, ensure waterproof sealing; Shielded compensating wire grounded at one end, keep away from power cables and drive cabinets; Protective tube damp: clean with alcohol and dry.
(4) Inaccurate temperature, large steady-state deviation Common causes:
Wrong type selected (mixing K/S/J/E), insufficient insertion depth, protective tube with coking or scale, medium corrosion, uneven temperature field Handling: Confirm correct type designation; Insertion depth ≥ 1/3 of the tube diameter, avoid touching tube walls; Clean protective tube of oil, dust, or coke deposits; For corrosive conditions, replace with corrosion-resistant, wear-resistant thermocouple. -
3. Simple Multimeter Test for Good or Bad (on-site operation)(1) Continuity / resistance measurement Normal:
tens to hundreds of ohms (depending on length) Infinite = open circuit, discard Near 0 ohms / conduction to ground = short circuit, leakage
(2) Millivolt judgment (precise) Heat the temperature sensing end, measure mV with an instrument; if the corresponding table shows a linear increase = normal; no change = damaged.
How to troubleshoot and locate faults in thermal resistors
RTD (PT100/PT1000) On-site Quick Fault Diagnosis and Solutions
-
1. First distinguish the wiring (key basics)2-wire: only measures resistance, large error, easy to drift 3-wire: industrial mainstream, compensates lead wire resistance, accurate temperature measurement 4-wire: high-precision laboratory use On-site, first verify the instrument configuration: it must match the actual wiring method.
-
2. Quick multimeter test (measure with power off)PT100 standard resistance at room temperature: 25°C ≈ 109.6Ω Normal:
resistance changes slowly and smoothly with temperature Resistance infinite → open circuit Resistance close to 0Ω → short circuit Resistance fluctuates → poor contact / damp leakage -
3. Common fault symptoms, causes, solutions(1) Instrument shows maximum value, overrange, HH Cause: RTD sensor wire broken, lead wire broken, terminal loose, internal burn-out Solution:
If multimeter measures infinite resistance, directly replace the probe Tighten terminals inside the panel, ensure proper crimping to prevent vibration loosening
(2) Displays negative numbers, temperature too low, fixed deviation Cause: Three-wire connected incorrectly (wrong color or random connection) Lead wire copper too long without resistance compensation Probe installed against pipe wall, not inserted deeply enough Solution:
Check the three wires by color group, reconnect correctly; ensure insertion depth ≥ 1/3 of the pipe, not touching the wall
(3) Temperature fluctuates, values drift Common causes:
Oxidized or loose terminal, damp/water ingress, insulation degradation, interference from power lines / frequency converters on the same cable tray Solution:
Clean oxidized terminals, tighten screws Dry the junction box, provide waterproof sealing, replace moisture-proof silicone Route signal wires separately, shielded end grounded, away from high-voltage power cables
(4) Temperature measurement inaccurate, large steady-state deviation Cause: Wrong model selected (mixing PT100/PT1000) Protective tube scaling, oil contamination, aging Environmental heat radiation, installation location dead spots Solution:
Verify nominal type; remove and clean protective tube dirt; adjust measurement point to avoid heat source dead spots
(5) Three-wire system gradually increases error Cause: Resistance of the three compensation wires is unbalanced Solution:
Check if the three wires have the same cross-section and length; enable three-wire compensation function on the instrument.
How to quickly locate and troubleshoot a malfunction in a hot gas mass flowmeter (3)
-
Step 1: Identify the fault phenomenonFirst, it is necessary to accurately identify the specific fault phenomena exhibited by the flow meter, which can help us quickly narrow down the scope of troubleshooting. Common breakdowns include: 1. No display: The screen does not light up at all. 2. There is flow but the reading is zero: There is gas flow in the pipe, but the meter shows zero. 3. No flow but no reading is zero: There is no gas flow in the pipeline, but the meter shows a flow value (zero drift). 4. Large fluctuations in readings: The flow display value is unstable and jumps frequently. 5. Low Measurement: The flow rate display value is consistently lower than the actual flow. 6. Abnormal output signal: The output signal such as 4-20mA or RS-485 does not match the displayed value.
-
Step 2: Locate the cause according to the phenomenonAccording to the fault phenomenon determined in the first step, in-depth investigation is carried out from the following aspects. 1. Power and display issues If the flow meter is not displaying, check in the following order: Check the power supply: Confirm that the power supply is turned on and the voltage is normal. Check the wiring: Check if the power cord polarity is reversed (especially when powered by 24V DC). Check the internal components: Observe if the power indicator lights up. If the light is on but the screen is not on, the display may be loose or damaged; If the light does not come on, the internal switching power supply may be damaged. 2. Media and process conditions Changes in the state and process of the gas being measured are common causes of abnormal readings. Gas Composition Variations: Confirm that the actual measured gas type is exactly the same as the internal settings of the flow meter. Changes in gas composition can directly affect thermal conductivity, leading to inaccurate measurements. Media contamination: If the gas contains impurities such as oil mist, water droplets, and dust, it will adhere to the sensor probe to form an "insulating layer", resulting in a decrease in heat transfer efficiency, manifested as low readings or zero readings in severe contamination. Media with Liquid or Gasification: The presence of droplets or liquid vaporization in the pipeline can significantly interfere with the heat exchange process, leading to wild fluctuations in readings or false flow rates during downtime. Flow Pulsation: Pulsating currents from upstream compressors, pumps, and other equipment, or frequent valve adjustments, can cause large fluctuations in readings. 3. Installation and piping environment Incorrect installation and complex piping environments can directly affect measurement accuracy. Improper Mounting: Installed near elbows, valves, or reducers, the flow meter can create turbulence, leading to large fluctuations in readings. It should be ensured that there are enough straight pipe sections in front and behind the flow meter (usually 10D before 5D, D is the pipe diameter). Incorrect probe installation: The probe is inserted at the wrong depth or in the wrong orientation, resulting in low or no readings. External interference: Strong electromagnetic devices such as frequency converters and large motors nearby may interfere with signal transmission, leading to fluctuations in readings or abnormal output signals. It is necessary to check whether the signal line shielding and grounding are good. Pipeline blockage: Foreign objects such as stones and welding slag in the pipeline may block the flow meter entrance, resulting in an abnormal increase in pressure drop and the flow rate cannot pass normally. 4. Meter settings and status Incorrect parameter settings or changes in the gauge's own state are also important troubleshooting points. Incorrect Parameter Settings: Check whether parameters such as range, gas type, flow unit, pipe diameter, etc. are set correctly. Incorrect settings are a common cause of inaccurate readings. Zero Drift: After a period of use, the meter may drift at the zero point, resulting in a non-zero display when there is no flow. Re-zeroing is required to ensure that there is no flow in the pipeline. Small Flow Exclusion: If a small flow cut value is set, traffic below that value is displayed as zero, which may mask the true small flow. Faulty Sensor/Electronic Components: Aging sensors, damage, or faulty internal circuitry can cause various abnormal readings, such as stuck readings, no output, or display error codes
-
Step 3: Execute the solutionPower Supply Problems: Check and connect the power supply to correct wiring polarity. Damaged internal components: contact the supplier for factory repair. Gas Composition Changes: Check and correct gas type settings within the meter. Sensor Contamination: Carefully clean the sensor probe using anhydrous ethanol and a soft cloth. Liquid/pulsating media: Gas-liquid separators, filters or buffer tanks are installed upstream. Improper installation position: Adjust the installation position to ensure sufficient straight pipe sections. Probe installation error: Reinstall according to the instructions, ensuring correct orientation and depth. External Interference: Check and improve the shielding and grounding of signal lines. Parameter setting error: Check and correct parameters such as range and unit. Zero Drift: Perform zero point calibration in a static no-flow state. The damping coefficient is too small: appropriately increase the damping (filtering) time to smooth the reading. Sensor damage: Contact the supplier for detection or replacement.
Fault and solution of RF admittance level switch
-
1. Not working at all: no display, no light, no actionTypical phenomena: no response to power-on, no indicator light, and no suction of the relay.
(1) Power supply problems (most common) Measured with a multimeter: 24VDC (±10%) or 220VAC is normal. Check: Empty, fuse, whether the terminal is loose / oxidized, whether the polarity is reversed. Handling: Replace the fuse of the same specification; Re-crimp the terminals; Correct positive and negative poles.
(2) Internal circuit failure Performance: The power supply is normal and still unresponsive, and the insurance is burned as soon as it is powered on. Treatment:
Most of the motherboard/power module is damaged→ Replace the meter head or return to the factory for repair. -
2. Short positions are also alarmed (false alarm, constant light)Typical phenomenon: the silo is empty, the switch still shows "charge", and the relay keeps sucking.
(1) Probe hanging/fouling (90% on-site causes) Reason: Dust, wet, and adhesive materials adhere to the probe and are regarded as "material". Treatment:
If the empty position is powered off, remove the probe and wipe it clean with anhydrous alcohol + soft cloth; After reloading, the short position is re-zeroed (key!). )。
(2) The sensitivity is too high Reason: If the adjustment is too sensitive at the factory or before, it will be triggered by a slight hanging. Processing: Adjust the sensitivity clockwise (generally there is a coarse C, a fine F), and the green light can be stable when the position is empty.
(3) Poor grounding/interference Reasons: No grounding, poor grounding, and a frequency converter / large motor nearby. Treatment:
The instrument shell is connected to the earth separately (not the neutral wire); Shielding wires for signal lines and away from power lines; If necessary, filter or change the installation position.
(4) The insulation of the probe is damaged Phenomenon:
The probe and silo wall resistance is very small (<100kΩ), water ingress/cracking. Treatment:
Replace the probe (not repairable). -
3. Do not call the police when there is material (omission, no action)Typical phenomena: no trigger when the material is full, the indicator light does not turn on, and the relay does not work.
(1) The sensitivity is too low Processing: Increase the sensitivity counterclockwise until the red light is on and the relay is in motion when the probe is expected.
(2) The probe is installed in the wrong position Reason: Loading too high/too low, too close to the wall, and being impacted by the material flow is crooked. Processing: Adjust to the normal submersion of the material level, and install it firmly vertically / horizontally.
(3) The probe is dirty but not clean Treatment:
Thorough cleaning + recalibration.
(4) The relay is damaged or the output is reversed Processing: Relay on and off; Check whether the normally open/normally closed (NO/NC) is reversed. -
4. Alarm jumping, relay jitter (unstable)(1) Material level fluctuation/material flow shock Treatment:
Increase the delay (5–10 seconds) to avoid instantaneous false triggers.
(2) Interference/poor grounding Treatment:
Grounding, shielding, and staying away from interference sources in the "false alarm".
(3) Probe looseness/vibration Handling: Tighten the probe and reinforce the mounting bracket. -
5. It is still not allowed after calibration/calibration(1) The empty position must be adjusted to zero and the full position must be calibrated Steps: Short position → zero (green light, no alarm); Let the material just pass the probe → adjust the sensitivity/calibration (red light on, alarm); Fix it and don't mess with the knob anymore.
(2) Change of medium (dry/wet, material change) Processing: recalibration; If necessary, replace the adaptive probe (e.g. insulating probe for conductive materials).
Malfunctions and Solutions of Input Liquid Level Sensor
Immersible Hydrostatic Level Sensor (Level Transmitter) Full Troubleshooting Guide + Solutions Applicable to: Water tanks, sewage tanks, deep wells, hydrostatic immersible 4-20mA level meters
-
I. Basic Quick Inspection(1) Power Supply Check Standard supply: DC 24V Measured below 18V → Excessive voltage drop, aging power source, wire gauge too thin Voltage normal but not working → Display circuit board failure
(2) Venting Pressure Tube (Most Critical, Often Overlooked) The immersible type uses negative pressure ventilation to compensate atmospheric pressure: Blocked vent, water ingress, condensation, bending → Zero drift, inaccurate readings Vent cable must not be submerged, blocked, or knotted
(3) Wiring Polarity and Shielding Reversed polarity: No display, no output Shield layer: Single-ended grounding, keep away from inverters and pump power lines
(4) Probe Diaphragm Bottom diaphragm covered with sludge, scale, debris, scratches → Low readings, stuck
(5) Installation Location Avoid water impact zones, vortex areas, pump intakes; prevent probe from being pressed on the bottom -
II. Typical Faults + Causes + SolutionsFault 1: Display shows full scale, value stuck at maximum Common Causes:
(1) Overload on diaphragm, sensor core damaged
(2) Signal line short-circuited, water infiltration
(3) Vent pressure blockage causing negative pressure imbalance Solution:
Remove and test in air: Normal zero → On-site water pressure/installation issue If still full scale → Probe burned out/core breakdown, replace directly Clean vent tube, dry internal condensation
Fault 2: Level does not move, fixed value, false level Common Causes:
(1) Probe buried in sludge, bottom sediment pressing diaphragm
(2) Vent tube blocked, condensation
(3) Range parameters mistakenly changed Solution:
Lift probe and rinse bottom diaphragm, remove sand and debris Clear vent cable and air-dry Verify 4mA = empty, 20mA = full, restore range settings
Fault 3: Level low, large measurement error, zero drift High-frequency core issue: Vent compensation failure Other causes: Diaphragm scaling, temperature drift, cable dampness Solution:
Drain tank and perform zero calibration Clean pressure-sensing diaphragm (rinse with soft water, no scraping with hard objects) Check vent cable for clear ventilation path, prevent rainwater backflow
Fault 4: Values jump, fluctuate, keep drifting Causes:
(1) Pump start/stop, water flow impact, vortex disturbance
(2) Poor cable shielding, inverter interference
(3) Oxidized terminals, poor contact, moisture leakage Solution:
Install anti-interference guard tube for probe, stabilize flow in stilling well Increase instrument filter damping time Retighten terminals, single-ended shield grounding, separate power lines
Fault 5: 4–20mA output abnormal, no current, current unchanged Troubleshooting: Measure current with no load: Should be around 4mA without water Circuit open / poor connection → redo connections Current stuck unchanged → circuit board damaged, return or replace
Fault 6: Water ingress, display condensation, internal leakage Causes:
Seal aging, cable root damage, long-term immersion Solution:
Short-term drying for emergency; Severe leakage requires direct replacement, not repair -
III. Quick On-Site Judgment with MultimeterMeasure power supply: DC 24V normal In air without water: Standard output ≈ 4mA, normal Significantly higher/lower/stagnant → Sensor fault Press diaphragm lightly: Current rises smoothly = Core intact No change/jumping = Damaged
How to quickly locate and troubleshoot a malfunction in a vortex flowmeter
Vortex Flowmeter On-site Quick Troubleshooting + Solution
Applicable: steam, gas, liquid, compressed air vortex pulse / 4-20mA type
-
1. The basic start-up must be checked(1) Power supply DC24V normal; Low voltage, large voltage drop, virtual connection, reverse connection→ no display, no output
(2) Installation of straight pipe section (vortex core) 10D ≥ front, 5D ≥ rear; valves, elbows, pumps, and diameter reductions are installed nearby→ and the metering is large/runout
(3) Grounding and interference Sensor shielding single-ended grounding; Stay away from frequency converters, motors, and power cables to prevent power frequency interference
(4) The lower limit flow rate under working conditions The vortex street has a starting flow, and the small flow is below the lower limit→ it does not go and is displayed as 0 -
2. Typical fault phenomena + causes + treatment(1) The pipeline has flow, and the instrument shows 0 and does not go out Common causes:
Actual flow rate is lower than starting flow rate (gas/steam is the most common) The probe swirl detects dirt, scale, water accumulation, and wear Pulse signal wire breakage, poor contact, motherboard amplification circuit damage The valve is not fully open and the throttling is serious Resolution:
Confirm whether the flow rate of the working condition is within the range; cleaning of vortex generators and probe impurities; Check that the wiring is tight and the shielding is intact; open upstream valves and rectify straight pipe sections; Replace the wide-range vortex street or booster under small flow conditions
(2) Traffic jumps, large fluctuations in value, and irregular drift Causes of high incidence: Pipe vibration, water hammer, pressure pulsation Strong electromagnetic interference (frequency conversion, welding machine) The damping filter setting is too small The medium contains liquid, impurities, and two-phase flow Resolution:
Menu increases software damping/filtering time; pipeline reinforcement and shock absorption, elimination of water hammer; Separate grounding, shielding and isolation, and separate wiring of power lines; Gas installation of steam and water separator and sewage discharge; Two-phase current is not suitable for vortex streets, replace other meters
(3) There is no medium in the air traffic tube, and the instrument is randomly measured and spontaneously pulsed Cause: Pipe vibration resonance Interference in series and poor grounding The probe is damp and the insulation falls The sensitivity is too high Resolution:
reduced trigger sensitivity; Improve grounding and shielding; Drying the junction box and making waterproof seals; Eliminate pipeline resonance and reinforce support
(4) The measurement is large/small, the accumulation is inaccurate, and the error is large Cause: The straight pipe section is insufficient and the installation is eccentric Medium temperature and pressure not compensated (steam/gas mandatory) Parameter settings: pipe diameter, coefficient, density, and range error The generator hangs dirt and changes the shape of the throttle Resolution:
rectification of the front and rear straight pipe sections, centered installation; The temperature and pressure compensation type must be invested in real-time temperature and pressure compensation; Check the K-factor and caliber unit of the instrument; disassemble and clean the vortex generator; Re-on-site calibration
(5) 4-20mA output abnormal, full load, no current, stuck Cause: Loop short circuit, disconnection, load resistance exceeding the standard The range is set incorrectly The motherboard DA conversion module is damaged Resolution:
universal meter measurement loop; Check 4mA zero flow rate and 20mA full flow; recalibrate analog outputs; Hardware damage returned to the factory
(6) Steam special is common: condensation, seismic gauge, reading floating Resolution:
Thermal insulation and heat tracing, bottom sewage discharge, shock absorbing bracket, increased filtering, and real-time compensation of temperature and pressure -
3. The multimeter is simple and quick to judge the quality of the meter(1) The power supply is normal 24V
(2) No flow: the pulse output has no jumping, and the current is stable at about 4mA
(3) Simulated airflow / touch probe: the pulse follows the change→ the probe is normal No change→ Sensing / Motherboard damage
How to quickly locate and troubleshoot a malfunction in a turbine flowmeter (2)
Turbine Flow Meter On-site Quick Troubleshooting + Full Solution Applicable: Liquid / Pure Water / Diesel / Lubricating Oil / Organic Solvent Pulse Type, 4-20mA Turbine
-
1. Pre-check
-
2. Typical faults + causes + precise solutionsFault 1: There is a flow rate in the pipeline, and the meter shows 0 and does not go count Core Reasons:
(1) The impeller is stuck, the bearing is worn and locked, and the debris is stuck
(2) The pre-filter is blocked, and there is no actual flow
(3) Pulse signal line breakage, shielding short circuit, probe failure
(4) The flow rate is lower than the starting flow, and the range selection is large Resolution:
(1) Disassemble and inspect the surface body, clean up impurities, manually toggle the impeller, and rotate smoothly to normal; Stuck replacement bearing/impeller
(2) Cleaning the pre-filter and dredging the sewage
(3) Use a multimeter to measure the pulse on and off, the quality of the induction probe, and redo the wiring
(4) Replace the micro/low starting flow turbine in small flow situations
Fault 2: Random traffic jumps, large and small values, and multiple metering for no reason Causes of high incidence:
(1) The medium contains bubbles, negative pressure intake, and the pipeline is not exhausted
(2) Pipeline vibration and electromagnetic interference (frequency converter, welding machine)
(3) The impeller is slightly scratched and the bearing clearance is large
(4) The sensitivity is too high and the filter damping is too small Resolution:
(1) Install an exhaust valve at the high point to eliminate air masses when the pipe is full
(2) Instrument enlargement software filtering/damping; Separate grounding, shielded single-ended grounding, away from power cables
(3) Disassemble and inspect and correct the impeller clearance and replace the wear parts
(4) Reduce the triggering sensitivity and suppress clutter false triggering
Fault 3: Measurement is too large/small, cumulative is inaccurate, and the error is excessive Cause:
(1) Installation inversion, insufficient straight pipe section, and sealing gasket protruding into the pipe
(2) Long-term wear: bearing and impeller wear, speed deviation
(3) Wrong parameters: the instrument coefficient K, caliber, density, and range are set incorrectly
(4) The viscosity of the medium does not match the calibration (high incidence of oil) Resolution:
(1) Check the flow direction arrow, rectify the straight pipe section, and trim the gasket
(2) Replace the movement assembly with serious wear
(3) Check the K factor of the factory nameplate and re-enter the configuration
(4) Recalibrate the high-viscosity medium or replace the adapted model
Fault 4: The air conditioning tube does not drain liquid, and the instrument automatically runs volume and emits false pulses Cause:
(1) The pipeline resonance and slight jitter drive the impeller to idle
(2) The induction probe is damp, the insulation drops, and the signal is interfered
(3) Negative pressure suction and trace air hammer disturbance at the installation position Resolution:
reinforced pipeline shock absorption; Drying junction box waterproof sealing; Optimized grounding shielding; Adjust the mounting point
Fault 5: Abnormal 4–20mA output, full scale, no current, stuttering Cause: Signal loop break/short circuit, load resistance exceeded limit, range configuration error, motherboard output damage Resolution:
multimeter measurement loop; Check 4mA zero flow rate and 20mA full flow; recalibrate the analog quantity; Hardware failure return to the factory for repair
Fault 6: Easy to stutter, short service life (common problem on site) Resolution:
Upstream standard filter + sewage discharge; Hard impurities are strictly prohibited; cemented carbide bearings are used for wear-prone media; Avoid dry rotation and idling -
3. Simple on-site quality judgment (no need to dismantle large pipes)
How to quickly locate and troubleshoot a pressure transmitter malfunction
-
1. First, divide the phenomena into three major categories:
-
2. Basic electrical troubleshooting (80% of faults occur here)(1) Check supply voltage Two-wire system: terminal measured DC 18–28V is normal Below 16V: excessive voltage drop, insufficient power capacity, long line loss High voltage: power supply voltage regulation damaged, may burn the mainboard
(2) Check loop current (core judgment) Normal:
4–20mA linearly corresponds to pressure under stable static pressure Fixed at 3.6mA: motherboard fault / sensor self-test error Fixed at 22mA: overrange, diaphragm overload damage Always 4mA: zero point stuck, impulse line blocked, no pressure applied
(3) Check wiring and continuity Check for reversed polarity, loose terminals, oxidation, poor connection Shielding layer should be grounded at one end only; grounding at both ends is prohibited (ground loop interference causes value jumps) Long lines should be checked for short circuits, insulation damage, water ingress -
3. On-site pressure and zero point calibration (quickly distinguish instrument or working condition)(1) Power off and restart: exclude freeze or software drift
(2) Release pressure to atmosphere to check zero Normal:
returns to 4mA, displays 0 Does not zero: zero point drift, locally reset zero using button Still off: sensor aging, diaphragm plastic deformation due to pressure
(3) Manual pressure application / compare with standard pressure gauge Follows linear change: instrument normal, on-site process pressure fluctuation Does not follow: transmitter body fault -
4. Impulse line & installation fault diagnosis (high frequency on site)(1) Impulse line blockage / crystallization / oil sediment accumulation Phenomenon:
pressure unchanged, slow response, stuck Action: clean, purge, insulation and heating, install buffer
(2) Pressure line air accumulation / air lock (liquid pipeline) Phenomenon:
value drift, slight fluctuation Action: vent at high points, route pipes reasonably
(3) Condensation water impact (steam measurement) Insufficient condensate in trap, direct high-temperature impact on diaphragm → temperature drift, damage
(4) Wrong installation position Pump outlet, elbows, turbulent areas → impact pulsation, unstable readings -
5. Interference, grounding, isolation problems (main cause of digital fluctuation)
-
6. Medium corrosion, diaphragm damage judgment
-
7. Safety precautions
Fault and solution of tuning fork level switch
-
1. First, Understand Normal Operating Logic(1) No-load: Tuning fork oscillates at high frequency, output shows no material signal
(2) Covered by material: Fork body damping stops oscillation → relay flips, output shows material alarm -
2. No response when powered, no detection, always shows no material
-
3. False alarm in empty bin, misoperation, always shows materialCore causes:
(1) Fork body adheres tiny powder, moist material, water condensation film, forming false damping
(2) Bin strongly vibrates, stirring resonance, causing tuning fork mis-stop
(3) Sensitivity set too high, slight interference triggers
(4) Junction box water ingress, poor sealing, circuit leakage Troubleshooting:
(1) Thoroughly clean fork body, dry to prevent moisture
(2) Lower sensitivity, enable delay filtering (0.5–3s debounce)
(3) Use shock-absorbing support, keep away from vibration sources, avoid resonance
(4) Check cable joints, potting and seal for waterproofing and moisture prevention -
4. Intermittent operation, sometimes works sometimes not, unstable fluctuationCore causes:
(1) Material dust floating, sparse material intermittently contacts fork body
(2) Electromagnetic interference: Inverter, power lines in same slot interfering with circuit
(3) Loose installation, slight fork body wobble Troubleshooting:
(1) Increase delay suppression, raise trigger threshold
(2) Run signal lines in separate conduits, away from power cables, shield with single-end grounding
(3) Reinforce flange / threaded base, eliminate looseness -
5. Corrosion, high temperature, aging failure(1) High temperature over limit: exceeding rated temperature → chip attenuation, stop vibration failure
(2) Acid/base corrosion: fork body thins, pitting, resonance frequency shifts Treatment:
Use high-temperature specialized model for high heat, use 316L / anti-corrosion coating model for corrosion -
6. Common human errors in electrical wiring(1) NO/NC normally open/normally closed reversed: alarm logic inverted
(2) Directly driving high-power load: contacts burned and stuck Correct: control via intermediate relay isolation, do not directly drive main circuit
Malfunction and solution of rotary material level switch
-
1. First, distinguish the 2 basic normal states:(1) No load, no material: motor rotates normally at a uniform speed
(2) Material blocked: blade gets stuck → stops rotating → internal micro switch activates, outputting alarm/shutdown signal -
2. Power on but not rotating, blade not movingCommon causes:
(1) Power supply abnormal: phase loss, AC220V/DC24V voltage mismatch, loose or oxidized terminals
(2) Internal motor burned out, reduction gear jammed
(3) Factory-set torque too high, cannot start under no load
(4) Main shaft or blade stuck by hardened material debris Troubleshooting: - Measure input voltage and tighten wiring - Manually rotate the blade: if it cannot rotate = mechanical jam, disassemble to clear material / replace module - Adjust torque knob lower under no load to restore normal rotation - If motor is silent and does not work: replace the motor assembly directly -
3. Continuous rotation, with material, but no alarm, no shutdownHigh-frequency issues:
(1) Light material (fly ash, wood powder, light calcium) has low friction, belt slips with no torque
(2) Torque adjustment too low, resistance does not trigger micro switch
(3) Blade size too small (standard S blade for light powders)
(4) Shaft bushing worn, slipping under no-load Solutions:
- Increase torque sensitivity - Replace with widened large three-blade special blade to increase force - Check main shaft clearance, replace the assembly if severely worn -
4. Empty hopper, no material, but continuous alarms or false actions(1) Internal dust accumulates, gears jammed, cannot reset
(2) Hopper vibration too large, vibrating module triggers falsely
(3) Material clinging to main shaft forms false resistance
(4) Internal micro switch sticking, contacts normally closed Solutions:
- Disassemble to clean dust and remove material from shaft - Install anti-vibration base, damping - Check switch contacts, replace internal components if stuck -
5. Frequent jamming, abnormal noise, severe vibration(1) Material falling directly onto blade, large pieces hitting and bending main shaft
(2) Bearing wear, eccentric rotation grinding the housing
(3) Incorrect vertical/angle installation, rubbing against pipe wall Solutions:
- Install anti-collision protection tube, impact shield - Side installation at 15–20° to avoid direct drop zone - Replace if main shaft is deformed -
6. Wiring and electrical logic faults(1) Normally open/normally closed reversed: alarm logic inverted
(2) Long-term heavy load, contact erosion
(3) Explosion-proof type sealed but water ingress or condensation short circuit Recommendation: only control intermediate relay, do not directly drive high-power load
How to install and use the product?
How to install and use an ultrasonic flow meter
-
I. Measurement principle and applicable contraindications
-
II. Rigid premise of installation (whether to determine whether it is accurate or not, whether it is stable or not)
-
III. Standard installation location
-
IV. Electrode selection and installation specifications
-
V. Wiring and power supply
-
VI. Commissioning steps (three key steps)
-
VII. Daily correct use judgment
-
VIII. Common faults + quick resolution
-
I. Measurement principle and applicable contraindications
-
II. Rigid premise of installation (whether to determine whether it is accurate or not, whether it is stable or not)
-
III. Standard installation location
-
IV. Electrode selection and installation specifications
-
V. Wiring and power supply
-
VI. Commissioning steps (three key steps)
-
VII. Daily correct use judgment
-
VIII. Common faults + quick resolution
Malfunction and solution of rotary material level switch
Ultrasonic Level Meter Standard Installation, Use, Commissioning, and Pitfall Avoidance Full Process (Field Universal Version)
-
1. Core Measurement Principle
-
2. Essential Selection & Working Condition Confirmation Before Installation
-
3. Standard Installation Location (Critical, Determines Accuracy)
-
4. Mechanical Installation Standards
-
5. Wiring and Power Supply
-
6. 5 Basic Parameters to Set at Startup (Inaccuracy if Not Set)
-
7. Normal Commissioning Judgment Standards
How to install and use a gear flow meter
Gear Flow Meter (Oval Gear / Waist Wheel / Mini Gear) Standard Installation, Use, and Quick Troubleshooting
-
1. Understand Applicable Conditions First
-
2. Pre-Installation Requirements (Determine Accuracy and Lifespan)
-
3. Straight Pipe and Flow Direction
-
4. Correct Installation Orientation
-
5. Wiring and Signals
-
6. Startup Steps (Must Follow Sequence)
-
7. Daily Usage Precautions
-
8. Common Faults and Quick Solutions
How to install and use an electromagnetic flow meter
Electromagnetic Flowmeter Standard Usage, Installation and Commissioning, Quick Troubleshooting
-
1. Core Principles & Applicable Contraindications
-
2. Four Mandatory Installation Conditions (most problems occur because these are not done)
-
3. Correct Installation Orientation
-
4. Standard Steps for Power-On and Commissioning
-
5. Normal Usage Judgment
-
6. Common High-Frequency Faults and One-Button Solutions
-
7. Usage and Maintenance Points
How to install and use a capacitive level meter.
Capacitive level gauge (RF capacitance / level switch / continuous measurement) installation + troubleshooting
-
I. Measurement principle and applicable contraindications
-
II. Rigid premise of installation (whether to determine whether it is accurate or not, whether it is stable or not)
-
III. Standard installation location
-
IV. Electrode selection and installation specifications
-
V. Wiring and power supply
-
VI. Commissioning steps (three key steps)
-
VII. Daily correct use judgment
-
VIII. Common faults + quick resolution
How to install and use a rotary paddle level switch.
Full guide for the installation and use of the anti-rotation level switch The core of the anti-rotation level switch relies on the motor to drive the rotation of the blades, stops when the material is blocked and outputs the switch signal, and the installation is divided into two mainstream methods: horizontal/vertical.
-
1. Preparation before installation
-
2. Three mainstream installation methods
-
3. Wiring steps (safety first)
-
4. Key debugging (determine accuracy)
-
5. Daily use and maintenance (extended life)
How to install and use a tuning fork level switch.
A complete guide to the installation and use of tuning fork level switches The tuning fork level switch uses piezoelectricity to drive the high-frequency vibration of the tuning fork, and when it is submerged in the material, the vibration frequency drops, the circuit detects and outputs the switch signal. The core of the installation is to avoid impact, fixed direction, tightly seal, stable wiring, no debugging, almost maintenance-free, suitable for liquid/powder/granules, and it is strictly forbidden to install the fork end upwards.
-
1. Preparation before installation (must-do)
-
2. Three major installation methods (core + taboo)
-
3. Wiring steps (minimalist, no debugging)
-
4. Use and debugging (almost free of adjustment)
-
5. Daily maintenance (super simple)
How to install and use a pressure transmitter.
How to Install and Use a Pressure Transmitter
-
1. Brief Introduction to Working Principle
-
2. Pre-Installation Inspection and Model Confirmation
-
3. On-Site Installation Specifications
-
4. Electrical Wiring
-
5. Commissioning and Zero/Span Adjustment
-
6. Daily Use and Maintenance Points
How to install and use a turbine flow meter.
Turbo Flow Meter Standard Installation and Operation Guide
-
I. Measurement Principle
-
II. Verification Before Installation
-
III. Rigid Pipe Installation Requirements
-
IV. Electrical Wiring
-
V. Start-up and Test Procedure
-
VI. Daily Proper Use
How to install and use a vortex flow meter.
Turbo Flow Meter Standard Installation and Operation Guide
-
I. Measurement Principle
-
II. Verification Before Installation
-
III. Rigid Pipe Installation Requirements
-
IV. Electrical Wiring
-
V. Start-up and Test Procedure
-
VI. Startup Procedure
-
VII. Daily Use and Maintenance
How to install and use a temperature transmitter.
Practical Guide for Integrated Installation and Use of Temperature Transmitters
-
I. Working Principle
-
II. Pre-Installation Checklist
-
III. Sensor Field Installation (Preliminary Requirements)
-
IV. Main Temperature Transmitter Installation
-
V. Standard Wiring (Common Error Points)
-
VI. Range Setting and Debugging
-
VII. Routine Use and Maintenance
-
Tighten terminals regularly to prevent oxidation and loose connection Check probe protective tube for corrosion, scaling, and damage Outdoor locations should be moisture-proof and waterproof; never open covers in explosive areas while powered Calibrate zero and full scale annually
How to install and use a submersible level meter.
Submersible hydrostatic level gauge standard installation and practical operation guide
-
1. Measurement principle
-
2. Check before installation
-
3. Correct installation on site
-
4. Electrical wiring specifications
-
5. Commissioning and calibration
-
6. Daily use and maintenance
How to install and use a RF admittance level switch.
RF Admittance Level Switch Standard Installation Practical Guide
-
1. Working Principle
-
2. Pre-Installation Checks
-
3. On-Site Installation Standards
-
4. Electrical Wiring
-
5. On-Site Commissioning and Calibration
-
6. Correct Daily Use & Maintenance
How to install and use a thermal gas flow meter.
Thermal gas mass flow meter (thermal diffusion type) installation and standard usage tutorial
-
1. Measurement principle
-
2. Pre-installation verification
-
3. Core installation specifications
-
4. Electrical wiring
-
5. On-site commissioning and commissioning
-
6. Key points for correct daily use
-
7. Maintenance
How to install and use a thermal resistance.
Practical Guide for Standard Installation and Use of Resistance Temperature Detectors (PT100/PT1000)
-
1. Basic Principle
-
2. Pre-Installation Check
-
3. Core Installation Standards
-
4. Wiring Methods
-
5. Commissioning
-
6. Routine Maintenance
How to install and use a thermocouple.
Practical Guide for Standard Installation and Use of Thermocouples
-
I. Basic Principle
-
II. Pre-Installation Check
-
III. On-Site Standard Installation
-
IV. Compensating Wire Connection
-
V. Commissioning and Calibration
-
VI. Routine Use and Maintenance
How to install and use a radar level meter.
The complete version of the radar level gauge installation is used
-
1. Core principles
-
2. Check and check before installation
-
3. Key installation positioning
-
4. Wiring and electrical wiring
-
5. Steps for submission and debugging
-
6. Daily use and maintenance
How to install and use a float switch.
-
I. Working Principle
-
II. Applications and Prohibitions
-
III. Cable Float Switch (Plastic Spherical Type) Installation and Use
-
IV. Rod Stainless Steel Float Switch Installation and Use
-
V. Commissioning and Testing Steps
-
VI. Common Fault Quick Handling
How to select a product?
How to select a PT100 temperature transmitter
-
Step 1: Match the PT100 sensor with wiring
-
Step 2: Select installation type
-
Step 3: Core electrical parameter selection
-
Step 4: Environment and safety (adapt to site conditions)
-
Step 5: Power supply and communication (final check)
How to select an ultrasonic flow meter
-
1. distinguish between two categories
-
2. Confirm the tested medium
-
3. Pipeline parameters must be checked
-
4. Flow rate & flow rate range
-
5. Accuracy level selection
-
6. Output & power supply signal (docking PLC/DCS)
-
7. Installation environment & protection level
-
8. Requirements for installing straight pipe sections
-
9. Quick selection recommendation template
How to select an ultrasonic level meter.
-
1. Suitable for Measurement
-
2. Core Measuring Distance & Range Selection
-
3. Medium Classification Selection
-
4. Installation Structure
-
5. Electrical Parameters (for integration with control system)
-
6. Explosion-proof & Corrosion-resistant Selection
-
7. Environmental Temperature and Pressure
-
8. Quick Selection One-Click Template
How to select a gear flow meter.
-
1. First, distinguish the types
-
2. Viscosity Matching
-
3. Flow Diameter Selection
-
4. Accuracy Grade Selection
-
5. Material Selection
-
6. Temperature & Pressure
-
7. Signal Output and Power Supply
-
8. Installation Requirements
-
9. Quick Selection Template for Scenarios
How to select an electromagnetic flow meter.
-
1. Electromagnetic Flowmeters Only Measure Conductive Liquids
-
2. Matching Pipe Diameter & Flow Rate
-
3. Liner Material Selection
-
4. Electrode Material Matching
-
5. Accuracy and Excitation Mode
-
6. Structural Type Differentiation
-
7. Pressure, Temperature, and Protection Level
-
8. Explosion-proof, Grounding, and Electrical Output
-
9. Quick Selection Scenario Templates
How to select a capacitive level meter.
-
1. Core Principle
-
2. Probe Rod Type Selection According to Working Conditions
-
3. Material Matching
-
4. Selection by Medium Dielectric Constant
-
5. Special Adaptation for Working Conditions
-
6. Electrical Output & Power Interface
-
7. Installation Methods
-
8. Quick Application Selection Template
How to select a float switch.
-
1. First, choose the major category (based on usage scenarios)
-
2. Material selection (determines corrosion resistance, temperature resistance, and lifespan)
-
3. Cable selection (key for cable floats)
-
4. Control point length and installation
-
5. Electrical parameter matching
-
6. Temperature condition matching
-
7. Special condition selection
-
8. Quick selection one-sentence template
How to select a radar level meter.
-
1. Understand the core advantages (why choose 80G)
-
2. Key 1: Determination of dielectric constant ε (the bottom line of whether it can be measured or not)
-
3. Key 2: Range & Blind Spot Reservation (Easiest to Choose Wrong)
-
4. Key 3: Antenna structure matching working conditions (anti-hanging, anti-condensation)
-
5. Key 4: temperature and pressure matching
-
6. Key 5: Install the interface form
-
7. Key 6: Precision, output, and power supply
-
8. Explosion-proof & protection
-
9. One-click selection template for working conditions
What factors need to be considered when selecting a thermocouple?
-
1. Thermocouple Type Selection (Step One, Determine Maximum Measurement Temperature)
-
2. Measurement Temperature and Margin
-
3. Protective Tube Material (Core for Corrosion Resistance, Wear Resistance, and Lifespan)
-
4. Structural Form
-
5. Installation and Fixing Method
-
6. Insertion Depth
-
7. Matching with Environmental Atmosphere (often overlooked, prone to aging)
-
8. Compensation Wire Matching (preventing cold junction error)
-
9. Response Speed, Vibration Resistance, Protection
-
10. Explosion Proof, Transmitter Output
What factors need to be considered when selecting a thermal resistance?
-
1. Graduation Number and Accuracy Class (Basic Key)
-
2. Temperature Measurement Range
-
3. Lead Wire Configuration (Determines Measurement Error)
-
4. Protective Tube Material (Core for Corrosion Resistance, Wear Resistance, and Lifespan)
-
5. Probe Structure and Installation Fixation
-
6. Response Time and Insulation Sealing
-
7. Environmental Condition Protection
-
8. Whether to Match with Temperature Transmitter
How to select a thermal gas mass flow meter
-
1: Clarify the characteristics of the gas medium
-
2: Determine the working condition parameters
-
3: Select the structure type and installation
-
4: Determine the electrical parameters and functions
How to select a RF admittance level switch
-
Step 1: Measure the characteristics of the medium clearly
-
Step 2: Analyze working conditions and environmental conditions
-
Step 3: Determine the installation method and probe structure
-
Step 4: Determine the electrical parameters and functions
How to select a submersible liquid level sensor
-
1. Applicable
-
2. Range selection
-
3. Probe core material & anti-clogging
-
4. Cable and ventilation structure
-
5. Temperature and accuracy level
-
6. Electrical output and power supply
-
7. Protection, explosion-proof, and installation
-
8. Quickly select the scene template
How to select a vortex flowmeter.
-
1. Confirm the applicable medium first
-
2. Brief description of measurement principles
-
3. Precise selection of pipe diameter & flow rate (the most important thing, don't be rigid according to the pipe)
-
4. Selection of body material
-
5. Temperature and pressure & compensation method (steam must see)
-
6. Accuracy level
-
7. Classification of installation structure
-
8. Rigid requirements for the front and rear straight pipe sections (the error of 90% is from here)
-
9. Electrical signal output
-
10. Explosion-proof and protection
-
11. Scene quick selection template
How to select a turbine flow meter.
-
Step 1: Define fluid properties
-
Step 2: Determine the working condition parameters
-
Step 3: Choose Functions and Structures
How to select a pressure transmitter
-
1. First distinguish the type of measurement
-
2. Range selection
-
3. Accuracy and stability grading
-
4. Diaphragm/wetted material
-
5. Structural form distinction
-
6. Pressure interface installation specifications
-
7. Electrical output & power supply (docking PLC/DCS)
-
8. Environmental protection & explosion-proof
-
9. Quick scene selection template
How to select a tuning fork level switch.
-
Step 1: Measure the characteristics of the medium clearly
-
Step 2: Analyze working conditions and environmental conditions
-
Step 3: Determine the installation method and electrical parameters
How to select an oil float switch.
-
Step 1: Clarify the characteristics of the measurement medium
-
Step 2: Analyze operating conditions and environmental factors
-
Step 3: Determine installation method and functional requirements
How to select a rotary paddle level switch.
-
1. Applicable
-
2. Shell protection and installation form
-
3. Blade selection
-
4. Torque sensitivity adjustment
-
5. Temperature level selection
-
6. Voltage & contact output
-
7. Explosion-proof & anti-corrosion
-
8. Strengthen the configuration under special working conditions
-
9. One-click quick selection template



