TUF-2000F Wall-mounted non-contact Ultrasonic Flow meter for AC220V or DC24V
Working Principle
The transit-time ultrasonic flow meter is based on the physical characteristic that the propagation speed of ultrasound in a fluid is affected by the flow velocity. The instrument installs a pair of sensors on both sides of the pipe, alternately transmitting and receiving ultrasound. When the ultrasound propagates downstream, the sound speed adds to the flow speed, shortening the propagation time; when propagating upstream, the sound speed counteracts the flow speed, lengthening the propagation time.
A high-precision timing circuit accurately measures the time difference between downstream and upstream propagation. This time difference is strictly proportional to the average flow velocity of the fluid: the faster the flow, the greater the time difference; when the fluid is stationary, the time difference is zero. The instrument's microprocessor, combined with user input parameters such as pipe diameter and material, converts the time difference into the instantaneous flow velocity through temperature compensation and flow field correction algorithms, and then multiplies it by the pipe cross-sectional area to obtain the volumetric flow rate.
This method has no mechanical moving parts and causes no pressure loss. It is particularly suitable for high-precision bidirectional measurement of clean liquids such as water and oil, making it the mainstream choice for industrial process control and trade settlement.
Product Features
- High Accuracy
- Wide measuring range ,Several types transducer for selection , pipe size from DN15 mm to DN6000 mm.
- High Reliability Adopt low voltage, multi-pulse technology to improve accuracy, useful life and reliability.
- Strong Anti-interference Dual-balance signal differential receiver/ driver circuit to avoid interference of converter, TV tower, high voltage line.
Product detail

Technical Specifications
|
Accuracy |
Better than ±1% |
|
Repeatability |
Better than 0.2% |
|
Principle |
Transit-time measuring principle |
|
Measurement |
500ms |
|
Display |
LCD with backlight, display accumulated flow/heat, instantaneous flow/heat, velocity, time etc. |
|
Output |
Analogue output: 4-20mA or 0-20mA current output. Impedance 0∼1kW. Accuracy 0.1%. |
|
OCT output: Frequency signal (1~9999HZ) |
|
|
Relay output: over 20 source signal (no signal, reverse flow etc.) |
|
|
RS485 serial port |
|
|
Input |
Three analogue input |
|
Three-wire PT100 resistor input (optional) |
|
|
Other functions |
Automatically record the totaliser data of the last 64 days / 64 months / 5 years; |
|
pipe material |
Steel, stainless steel, cast iron, cement pipe, copper, PVC, aluminum, FRP etc. Liner is allowed |
|
pipe Size |
15-6000mm |
|
pipe Straight pipe section |
in the upstream it must be beyond 10D, in the downstream it must be beyond 5D, in the upstream the length must be beyond 30D from |
|
Liquid Types |
Water, sea water, industrial sewage, acid & alkali liquid, alcohol, beer, all kinds of oils which can transmit ultrasonic single |
|
Liquid Temperature |
Standard: -30 ℃ - 90 ℃ ,High-temperature:-30 ℃ - 160 ℃ |
|
Liquid Turbidity |
Less than 10000ppm, with a little bubble |
|
Flow Direction |
Bi-directional measuring, net flow/heat measuring |
|
Environment Temperature |
Main Unit: -30 ℃ - 80 ℃ |
|
Transducer: -40℃ -110℃, Temperature transducer: select on enquiry |
|
|
Environment Humidity |
Main Unit: 85% RH |
|
|
Transducer: water-immersible, water depth less than 3m |
|
Cable |
Twisted Pair Line, standard length of 20m, can be extended to 500m (not recommended); Contact the manufacturer for longer cable |
|
Power Supply |
AC220V or DC24V |
|
Power Consumption |
Less than 1.5W |
|
Protocols |
MODBUS, M-BUS, Fuji extended protocol and other factory protocol |