TUF-2000S Wall-mounted Ultrasonic Flow meter for DN15 ~ DN6000

Wall-mounted ultrasonic flowmeters are a common installation type of ultrasonic flowmeter, specifically referring to designs where the transmitter (main unit/converter) is structured to be mounted on walls, control cabinet panels, or brackets. This type is usually used in conjunction with clamp-on sensors or insertion sensors and is widely applied in long-term flow monitoring at fixed sites. The following are detailed application scenarios and selection points:
Split type: The sensor (probe) is installed on the pipeline and connected to the wall-mounted main unit via a shielded cable. This method facilitates reading and maintenance, and the main unit is not affected by pipe vibrations or high temperatures.
Housing design: It usually adopts a robust cast aluminum material and has a high protection rating (IP65/IP67) to suit industrial site environments.

    Working Principle

    The time-difference method is usually used, where an external clamp-on sensor emits and receives ultrasonic waves, measures the difference in propagation time of the ultrasonic waves in the fluid in the downstream and upstream directions, and then calculates the fluid flow velocity. Combined with parameters such as the pipe's cross-sectional area, the flow rate can be determined.

    Product Features

    1. A. Easy Installation, User-Friendly Interaction
      High Visibility: Once wall-mounted, operators can read the large LCD screen at eye level and view real-time data such as instantaneous flow, cumulative flow, flow velocity, and signal strength.
      Convenient Operation: Buttons or touchscreens are positioned at wall height, making it easy to set parameters on-site, navigate menus, and troubleshoot without climbing pipes or using ladders.
      Flexible Wiring: Sensor cables can be laid along wall grooves, neat and aesthetically pleasing, meeting industrial site management requirements.

      B. Powerful Functional Integration
      Multiple Outputs: Typically equipped with 4-20mA current output (remote transmission to PLC/DCS), pulse output (total counting), and relay alarm output (upper and lower limit alarms).
      Communication Interfaces: Built-in RS485 (Modbus RTU), M-Bus, and even Ethernet/Wi-Fi/4G modules, easily connecting to SCADA systems or IoT cloud platforms for remote monitoring.
      Data Recording: High-end models come with large-capacity storage (such as SD card or internal Flash), automatically recording historical flow data (daily/monthly/yearly reports), supporting USB export for trade settlement and energy consumption audits.
      Heat Calculation (Optional): When equipped with a temperature sensor, it can be directly used as an ultrasonic heat meter to calculate cold/heat energy, commonly used in HVAC systems.

      C. Environmental Adaptability and Safety
      Protection Level: Standard configurations are usually IP65 (water spray-proof) or IP67 (short-term immersion-proof), and some explosion-proof models can reach Ex d IIB T4, suitable for hazardous areas.
      Interference Resistance: Internal circuits are designed with strict electromagnetic compatibility (EMC) measures, resisting electromagnetic interference from variable frequency drives, motors, and other industrial equipment to ensure stable measurements.
      Wide Temperature Operation: Suitable for ambient temperatures from -20℃ to 60℃ (or even wider).

      D. Measurement Performance (Inheriting Ultrasonic Characteristics)
      No Flow-Blocking Components: When used with clamp-on sensors, there is no pressure loss in the pipeline.
      High Range Ratio: Can reach over 1:100, suitable for conditions with large flow fluctuations.
      Bidirectional Measurement: Simultaneously measures forward and reverse flow.

    Product detail

    ESMTUF2000S-p-1ESMTDS100F-p-1

    Technical Specifications

    Accuracy

    Better than ±1%

    Repeatability

    Better than 0.2%

    Principle

    Transit-time measuring principle

    Measurement
    Period

    500ms

    Display

    LCD with backlight, display accumulated flow/heat, instantaneous flow/heat, velocity, time etc.

    Output

    Analogue output: 4-20mA or 0-20mA current output. Impedance 0∼1kW. Accuracy 0.1%.

    OCT output: Frequency signal (1~9999HZ)

    Relay output: over 20 source signal (no signal, reverse flow etc.)

    RS485 serial port

    Input

    Three analogue input

    Three-wire PT100 resistor input (optional)

    Other functions

    Automatically record the totaliser data of the last 64 days / 64 months / 5 years;
    The power-on time and corresponding flow rate of the last 64 power on and off events. Allow manual or automatic flow loss
    compensation
    The instrument working status of the last 64 days

    pipe material

    Steel, stainless steel, cast iron, cement pipe, copper, PVC, aluminum, FRP etc. Liner is allowed

    pipe Size

    15-6000mm

    pipe Straight pipe section

    in the upstream it must be beyond 10D, in the downstream it must be beyond 5D, in the upstream the length must be beyond 30D from
    the access of the pump. (D stands for pipe diameter)

    Liquid Types

    Water, sea water, industrial sewage, acid & alkali liquid, alcohol, beer, all kinds of oils which can transmit ultrasonic single
    uniform liquid

    Liquid Temperature

    Standard: -30 ℃ - 90 ℃ ,High-temperature:-30 ℃ - 160 ℃

    Liquid Turbidity

    Less than 10000ppm, with a little bubble

    Flow Direction

    Bi-directional measuring, net flow/heat measuring

    Environment Temperature

    Main Unit: -30 ℃ - 80 ℃

    Transducer: -40℃ -110℃, Temperature transducer: select on enquiry

    Environment Humidity

    Main Unit: 85% RH

     

    Transducer: water-immersible, water depth less than 3m

    Cable

    Twisted Pair Line, standard length of 20m, can be extended to 500m (not recommended); Contact the manufacturer for longer cable
    requirement.
    RS-485 interface, transmission distance up to 1000m

    Power Supply

    AC220V or DC24V

    Power Consumption

    Less than 1.5W

    Protocols

    MODBUS, M-BUS, Fuji extended protocol and other factory protocol