UC2000-F36 2000mm Ultrasonic Proximity Switch Sensor for Automatic Industrial Control Equipment
Working Principle
The ultrasonic proximity switch's transmitter emits high-frequency ultrasonic waves. When these waves encounter an object, they are reflected back. The receiver captures the reflected echoes, and by measuring the time it takes for the ultrasonic waves to travel from transmission to reception, and combining this with the propagation speed of ultrasound in air, the distance between the sensor and the object can be calculated. When the distance reaches a preset threshold, the switch outputs the corresponding signal.
Product Features
1. Non-contact measurement: No physical contact with the target object is required, suitable for detecting fragile, high-temperature, corrosive, or moving objects.
2. Strong anti-interference capability: Not affected by the object's color, transparency, or material (such as glass, plastic, liquid, powder), and can operate stably even in harsh environments like dust or smoke.
3. Multiple output options: Supports switching output (such as NPN/PNP), analog output (4-20mA/0-10V), and IO-Link digital interface, making it easy to integrate with PLCs, data acquisition systems, or intelligent control systems.
4. Compact structure and easy installation: Square plastic or metal housing design, small in size, suitable for installation in space-limited equipment; some models have IP67/IP68 protection ratings, waterproof and dustproof, suitable for outdoor or humid environments.
5. Wide measurement range: Depending on the model, detection distances can range from a few centimeters to several meters; some models support background suppression function, allowing precise detection of objects within a specific distance while ignoring background interference.
application scenarios
1. Non-contact measurement: No physical contact with the target object is required, suitable for detecting fragile, high-temperature, corrosive, or moving objects.
2. Strong anti-interference capability: Not affected by the object's color, transparency, or material (such as glass, plastic, liquid, powder), and can operate stably even in harsh environments like dust or smoke.
3. Multiple output options: Supports switching output (such as NPN/PNP), analog output (4-20mA/0-10V), and IO-Link digital interface, making it easy to integrate with PLCs, data acquisition systems, or intelligent control systems.
4. Compact structure and easy installation: Square plastic or metal housing design, small in size, suitable for installation in space-limited equipment; some models have IP67/IP68 protection ratings, waterproof and dustproof, suitable for outdoor or humid environments.
5. Wide measurement range: Depending on the model, detection distances can range from a few centimeters to several meters; some models support background suppression function, allowing precise detection of objects within a specific distance while ignoring background interference. ...
Product detail


Technical Specifications
|
Product model |
UC500-F36-E4-V15 |
UC1000-F36-E4-V15 |
UC2000-F36-E4-V15 |
|
UC500-F36-E5-V15 |
UC1000-F36-E5-V15 |
UC2000-F36-E5-V15 |
|
|
Detection range |
50...500mm |
70...1000mm |
80...2000mm |
|
Detect dead zones |
0...50mm |
0...70mm |
0...80mm |
|
Transducer frequency |
About 380khz |
About 205khz |
About 180khz |
|
Response time |
About 50ms |
About 125ms |
About 150ms |
|
Switching frequency |
≤10Hz |
≤3Hz |
≤3.3Hz |
|
Output type |
E4 NPN NO/NC |
||
|
E5 PNP NO/NC |
|||
|
Operating voltage |
10-30VDC ripple 10% |
||
|
Rated operating current |
200mA short-circuit protection/overload protection |
||
|
Repeatability |
≤0.5% |
||
|
Range adjustment |
The farthest and closest ranges are adjusted by the adjustment line |
||
|
Degree of protection |
IP65 |
||
|
Connection method |
V15 (5-pin) M12 cable/2m PVC cable |
||
|
LED yellow light |
The switch status indicates that the yellow light is flashing The target is detected in the set state |
||
|
LED red light |
Solid red light: Error Flashing red light: No target detected in the set state |
||
|
Product model |
UC500-F36-E6-V15 |
UC1000-F36-E6-V15 |
UC2000-F36-E6-V15 |
|
UC500-F36-E7-V15 |
UC1000-F36-E7-V15 |
UC2000-F36-E7-V15 |
|
|
Detection range |
50...500mm |
70...1000mm |
80...2000mm |
|
Detect dead zones |
0...50mm |
0...70mm |
0...80mm |
|
Transducer frequency |
About 380KHZ |
About 205KHZ |
About 180KHZ |
|
Response time |
About 50ms |
About 125ms |
About 150ms |
|
Switching frequency |
≤10HZ |
≤3HZ |
≤3.3HZ |
|
Output type |
E6:Two ways PNP NO/NC |
||
|
E7:Two ways NPN NO/NC |
|||
|
Operating voltage |
10-30VDC ripple 10% |
||
|
Rated operating current |
200mA short-circuit protection/overload protection |
||
|
Repeatability |
≤0.5% |
||
|
Range adjustment |
The farthest and closest ranges are adjusted by the adjustment line |
||
|
Degree of protection |
IP65 |
||
|
Connection method |
V15 (5-pin) M12 cable/2m PVC cable |
||
|
LED yellow light |
The switch status indicates that the yellow light flashes and the target is detected in the set state |
||
|
LED red light |
Solid red: Error Flashing red light: No target detected in the set state |
||
|
Product model |
UC500-F36-I-V15 |
UC1000-F36-I-V15 |
UC2000-F36-I-V15 |
|
UC500-F36-U-V15 |
UC1000-F36-U-V15 |
UC2000-F36-U-V15 |
|
|
Detection range |
50...500mm |
70...1000mm |
80...2000mm |
|
Detect dead zones |
0...50mm |
0...70mm |
0...80mm |
|
Transducer frequency |
About 380KHZ |
About 205KHZ |
About 180KHZ |
|
Response time |
About 50ms |
About 125ms |
About 150ms |
|
Standard target board |
100mm*100mm |
||
|
Output type |
I:4-20mA |
||
|
U:0-10V |
|||
|
Operating voltage |
10-30VDC ripple 10% |
||
|
Rated operating current |
200mA short-circuit protection/overload protection |
||
|
Repeatability |
≤0.1% |
||
|
Range adjustment |
The farthest and closest ranges are adjusted by the adjustment line |
||
|
Degree of protection |
IP65 |
||
|
Connection method |
V15 (5-pin) M12 cable/2m PVC cable |
||
|
LED yellow light |
The switch status indicates that the yellow light flashes and the target is detected in the set state |
||
|
LED red light |
Solid red: Error Flashing red light: No target detected in the set state |
||